1 | DC fan | 12 | 36 | 432 | 6 | 2592 |
2 | Energy Saver Lights | 12 | 12 | 144 | 6 | 864 |
| | | | 576 | | 3456 |
| | | | | | |
| Load = | | | | 3456 | WH |
| Current required for Aplinces | Total watts/System voltage | | | 48 | A |
| Average daily sunny hours in project area | | | | 12 | hrs |
| Required Backup time | | | | 2 | hrs |
| System Voltage | | | | 12 | V |
| Design of Battery | | | | | |
| Backuptime (Hr)xLoad(watts)/System voltage | | | | 96 | Ah |
| add Eff. @ 90 % | | | | 106.666666667 | Ah |
| add 80 % DoD | | | | 133.333333333 | Ah |
| Des Amp. Hrs | | | Say | 133 | Ah |
| Proposed Battery Size | | | | 155 | Ah |
| No of Batteries | | | | 0.858064516129 | No |
| | | | Say | 1 | No |
| Design of Solar Panels | | | | | |
| Current required for Applinces = total watts/system voltage | | | | 48 | A |
| Current required for Battery = 60% DoD/average daily sunny hrs | | | | 11.1111111111 | A |
| Total current required | | | | 59.1111111111 | A |
| Lets Take currents for applinces | | | | | |
| Power for Solar Panel required = total current required x system voltage | | | | 576 | W |
| add 20 % losses ( lossess + conductor effeiciency) | | | | 691.2 | W |
| Proposed Size of panel | | | | 250 | No |
| No of Panels | | | | 2.7648 | No |
| | | | Say | 3 | No |
| Design of Charge Controller | | | | 57.6 | A |
| Proposed Size of Charge controler | | | | 60 | A |
| No of Charge Controlers | | | | 0.96 | No |
| | | | say | 1 | No |
| for safety of battery proposed 01 charge controlers of 12v/60A. | | | | | |